﻿### Activate minimum signal duration

This parameter decides whether the channel is to work with a definable time for the signal debouncing or a minimum signal duration for "0" or "1" signals with the configured pulse meter function.

In the "active" setting, additional parameters that define the minimum signal duration for "0" and "1" signals become visible. In the "inactive" setting, the device works with a debouncing time in milliseconds defined by the parameter of the same name.

### for "0" signal

This parameter defines the time of the minimum signal duration for "0" signals. When the pulse counter function is configured, the period during which a pulse must be present until a valid pulse is identified is defined for the input via the minimum signal duration.

A minimum signal duration of 0 min | 0 s | 15 ms to 59 min | 59 s | 999 ms can be set.

### for "1" signal

This parameter defines the time of the minimum signal duration for "1" signals. When the pulse counter function is configured, the period during which a pulse must be present until a valid pulse is identified is defined for the input via the minimum signal duration.

A minimum signal duration of 0 min | 0 s | 15 ms to 59 min | 59 s | 999 ms can be set.